VFD Application Notes: Flying Start and KEB’s Speed Search Technology

您的當(dāng)前位置: 首 頁 >> 新聞中心 >> 技術(shù)知識

VFD Application Notes: Flying Start and KEB’s Speed Search Technology

發(fā)布日期:2018-12-13 作者: 點(diǎn)擊:

In this series of blog posts, we will look at some special functions available in KEB drives – like the F5 VFD or S6 Servo Drive.

 

In this post we will discuss the Speed Search or “Flying Start” function.

 

What is Speed Search/Flying Start?

KEB F6 Drives with Speed Search Flying Start technology

 

Typical motor control applications utilizing a variable frequency drive (VFD) start the motor from zero speed. The VFD then controls the motor to the specified set speed using acceleration and deceleration rates as defined in the drive.

 

It is possible that application conditions may result in the motor rotating while the VFD output modulation is off. For example, if during operation, the modulation to the motor is removed, the motor will be free to coast. This coasting situation may be a result of a loss of input voltage to the VFD or due to a control command of the system.

 

If the modulation is again initiated to the motor (main power comes back online or control system command is given, for example) and the motor is still rotating due to the inertia of the load, attempting to control the motor from zero speed may cause high mechanical vibrations, high current in the motor, and possibly damage to gearboxes or couplings.

 

To help in this situation, KEB has developed a drive function we call Speed Search. This function is also known by some other names such as Flying Start or Catch-on-the-Fly.  When the Speed Search function in the KEB VFD is activated, the VFD will search for the actual speed of the motor and use this value as the starting point for the motor control, rather than zero speed. The KEB drive allows the Speed Search to be active after main power on, at error reset, at auto-restart or after modulation to the motor is initiated by the VFD.

 

Perform flying start - program Variable Frequency Drive

 

Flying Start function in use

As an example, let’s consider an application using a KEB VFD to control a motor running a large ventilation fan. In this application, the KEB VFD has the Speed Search programmed to be activated whenever the VFD is powered on. During normal operation, the building power is lost. Once the main power is lost, there is some residual power stored in the capacitors of the KEB VFD so it will not power down immediately. Once the power utilized by the ventilation fan system drops the VFD DC bus to the low enough level, the KEB VFD will power down. When the KEB VFD powers down, the modulation to the motor is removed and the fan motor is free to spin.

 

Depending on the inertia of the fan and the application setup, the fan may take some time before it comes to a stop. If power is restored before the fan has come to a stop the KEB VFD will actively search for the actual speed of the motor then use this value as the starting point for the ramp up to the commanded set speed.

 

In this case, the speed search function would provide a smooth control of the motor back up the set command speed minimizing any stress on the mechanical components and bring the system back to normal operation automatically.

 

KEB’s Speed Search can also be used when the motor is rotating in the opposite direction of the desired speed set point. For example, if the modulation to the motor of a blower system is removed and there is some residual pressure or back flow, this may cause the motor to rotate in the reverse direction as defined by the application.

 

If the modulation to the system is restored and the speed search function is activated, the KEB drive can determine the motor direction is not the same as the desired set point direction and, utilizing the protective functions of the drive, return the system to the desired setpoint speed and direction. In this case, once the KEB VFD has determined the motor speed is not in the same direction as the desired set point, utilizing the LA stop protective function of the drive, the KEB VFD first decelerates the motor to zero speed and then accelerates the motor in the forward direction to the command speed.

 

 

Comparison of different implementations

The speed search function of the KEB VFD in an open loop system works by monitoring the active current of the motor. The active current is the torque producing current. The speed search function utilizes the current command frequency or last known frequency as the starting point for determining the motor speed. If the application control is such that the command frequency is not changed very often, then using the command frequency as the starting point for the speed search function works well. If the command frequency may change during operation, then using the last known frequency is a good option.

 

When the speed search function is activated, the output frequency to the motor is set to either the command frequency or the last known frequency as programmed in the speed search options. The output voltage to the motor is then increased if the output phase current to the motor reaches the level defined in the speed search setup, the VFD then starts to lower the set frequency by the rate defined in the speed search setup. The default value of this current level is 80% of the VFD rated current.

 

As the output frequency is dropped, the active current to the motor will increase. Once the active current stops increasing, this indicates that the output frequency to the motor matches the actual speed of the coasting motor. The KEB VFD then keeps the output frequency constant while the output voltage is increased at a rate defined in the speed search options. The output voltage rate of increase may need to be changed if the load on the motor is such that the actual speed drops too low during the time the output voltage, and thus the motor torque, is increased. Testing of the system settings may have to be done to find the best solution for the application. The output frequency is kept constant for a short time at which point the KEB VFD switches into standard operation and accelerates the system to the command speed.

 

Using Command Frequency

Figure 1 is a scope trace using the KEB Combivis software of the Speed Search function in operation. In this case, the modulation to the motor was shut off allowing the motor to coast. The noted points on the graph represent the following:

 

  1. Coasting motor speed

  2. Modulation to the motor engaged, Speed Search active.

  3. Output frequency (red) initially set to command frequency. As output voltage (yellow) is increased, the phase current (blue) increases. Phase current reaches the 80% level as defined in the Speed Search function.

  4. Output frequency is reduced per the Speed Search setup.

  5. Motor torque current (green) stops increasing. Motor speed determined.

  6. Output frequency stays constant and the output voltage is increased. After a short time, the VFD resumes normal operation and continues to command speed.

 

speed search flying start technology

Figure 1 Flying Start – Command Frequency [Click to enlarge]

Using last known frequency output

In applications that may have changing set speeds, the KEB speed search function can also be set to use the last know frequency output as the starting point for the speed search function. Depending on how long the modulation to the motor is removed, this may allow the speed search function to determine the motor speed in a timelier manner.

 

Figure 2 is an example of the speed search function with the last known frequency used as the starting point. Notice that the last instance of the speed search function activating, the modulation was removed from the motor during the deceleration of the motor. The speed search then uses the frequency that was last known even though the system had not reached the programmed set point.

 

speed search flying start technology

Figure 2 Flying Start – Using last known frequency [Click to enlarge]

 

Catching a Motor spinning in the opposite direction

Figure 3 shows the KEB speed search function when the motor is rotating in the opposite direction of the commanded set point. In this case, when the speed search function is activated, once the phase current (blue) level is reached, the output frequency (red) to the motor is reduced until the magnetizing current (green) drops. In this case, since the motor is rotating in the reverse direction from the initial starting output frequency, the speed search function drops the output frequency to zero. After a short time, the system goes into the normal operation and the current limiting functions of the drive are utilized to bring the motor to a stop and then accelerate it to the command frequency.

 

speed search flying start technology

Figure 3 Flying Start – Catching motor from opposite direction [Click to enlarge]

 

Summary

The KEB speed search function is one of many powerful, standard functions available with KEB VFD’s. The above examples were done in an open loop control. The KEB closed loop VFD’s also have the speed search function. The function works very similar to the open loop version, but the closed loop will utilize the measured frequency from the feedback device as the starting point for the speed search function.

 

Properly utilizing this function can help reduce mechanical stress on components and help reduce potential downtime of your system when momentary interruptions to the operation occur.